oplossen van problemen met ro-membranen starts with data: normalized permeate flow, salt rejection, and differential pressure. This guide shows the fastest checks, a symptom-to-cause matrix, and exact tests and fixes for 1812/4040/8040 systems.
CIP and Cleaning Guide Replacement Checklist
Quick Checks
- Confirm valves and orientation: feed open, concentrate partially throttled, permeate to drain during start-up.
- Bypass tanks and post-filters during testing to remove backpressure effects.
- Replace clogged cartridges and verify dechlorination before TFC membranes.
- Record temperature, pressure at feed/concentrate/permeate, and TDS of feed and permeate.
ro membrane troubleshooting — key causes and thresholds
Effective oplossen van problemen met ro-membranen focuses on three signals: normalized permeate flow, salt rejection, and differential pressure. Clean when normalized flow drops about 10–15% or when ΔP exceeds supplier limits. Replace when rejection or flow cannot be restored to 90–95% of the clean baseline, or when oxidation damage or leakage is confirmed at end caps or interconnectors.
Always compare data at similar temperature and recovery. Many “low-flow” complaints are seasonal temperature effects; many “high-TDS” cases are actually backpressure from tanks or valves. Normalize first, then diagnose.
Symptom-to-Cause Troubleshooting Matrix
Symptom | Likely Causes | Tests | Fix |
---|---|---|---|
Low permeate flow | Fouled membrane; clogged cartridges; low feed pressure; cold water; recovery too high | Normalized flow vs baseline; ΔP per stage; check pump curve and temp | CIP for the fouling type; replace cartridges; raise pressure within limits; reduce recovery |
High permeate TDS / poor rejection | Oxidation damage; membrane end-cap leak; interconnector issue; extreme recovery | Salt rejection test; check chlorine upstream; pressure hold test; inspect seals | Replace damaged elements; fix leaks and orientation; correct recovery and backpressure |
High differential pressure (ΔP) | Particulate/colloidal fouling; biofouling; iron/manganese scale | SDI/NTU; ATP/biological tests; Fe/Mn tests; visual sludge | Alkaline CIP for organics/bio; dispersant; reducing agent for iron; improve pretreatment |
Frequent cleanings but no recovery | Wrong chemistry/temperature; irreversible damage; persistent upstream issue | Post-CIP rejection/flow vs baseline; inspect for oxidation; review antiscalant dosing | Switch chemistry and temp; repair root cause; schedule replacement |
Noisy pump / cavitation | Starved suction; blocked strainers; air ingress | NPSH check; suction pressure; inspect for air leaks | Open valves; clean strainers; fix suction plumbing and priming |
Key Tests: Rejection and Normalized Flow
Acceptance criteria and baselines
- Set a clean baseline for each stage: normalized permeate flow, rejection, and ΔP at reference temperature.
- Use the same meters and units to avoid false trends; document every CIP and changeout.
- During oplossen van problemen met ro-membranen, test with permeate to drain so backpressure does not distort readings.
Salt Rejection (single-pass)
Rejection (%) = (1 − permeate TDS / feed TDS) × 100. Compare to your new-element baseline under similar temperature.
Normalized Permeate Flow
Correct flow to a reference temperature and pressure so day-to-day results are comparable. Most suppliers provide a correction factor table or equation. Track normalized flow per stage and compare with the clean baseline.
ro membrane troubleshooting — step-by-step rejection test
- Flush to stable operation; divert permeate to drain for several minutes.
- Measure feed and permeate TDS and temperature with calibrated meters.
- Compute rejection and record alongside pressure and flow.
- If rejection falls beyond acceptance criteria and does not improve after CIP, schedule replacement.
See the full cleaning procedure in RO membrane cleaning.
This checklist shortens oplossen van problemen met ro-membranen by confirming valves, removing backpressure, and normalizing data before deeper tests.
Log results after every oplossen van problemen met ro-membranen session so future drift is obvious and preventive actions can be scheduled.
Sensor and Setup Errors
- Miscalibrated TDS or conductivity meters cause false rejection alarms; calibrate regularly.
- Permeate backpressure from tanks or valves inflates TDS and reduces flow; test to drain.
- Mixed units or wrong temperature input during normalization leads to false trends.
Clean or Replace?
- Clean when normalized flow drops about 10–15 percent or ΔP exceeds limits.
- Replace when rejection or flow cannot be restored to 90–95 percent of baseline or oxidation/leakage is found.
Follow the RO membrane replacement checklist for safe changeout.
Preventive Maintenance
- Maintain SDI ≤ supplier limit and change cartridges on pressure drop, not just on calendar.
- Verify antiscalant dosage and pH; dechlorinate upstream of TFC membranes.
- Log normalized flow, rejection, and ΔP per stage; trend weekly to catch drift early.
For element format and vessel interfaces, see 4040 vs 8040 ro membraan en bwro vs swro membraan.
Common mistakes that waste time
- Comparing raw (unnormalized) flow from winter to summer and calling it a failure.
- Running TFC membranes with residual chlorine; rejection will never recover after oxidation.
- Testing through tanks and post-filters; permeate backpressure inflates TDS and reduces flow.
- Cleaning with the wrong chemistry or too cold; organics/bio need warm alkaline with surfactant before acid.
References
DuPont FilmTec RO/NF Technical Manual | AMTA Fact Sheet – Cleaning in Place (CIP)
FAQs
What is an acceptable salt rejection for a new element?My flow is fine but TDS is high. What should I check?ΔP climbs within days after cleaning. Why?
For a complete changeout workflow after oplossen van problemen met ro-membranen, see our RO membrane replacement guide.
Need Help with a Live Issue?
Send feed TDS/temperature, stage pressures, normalized flow, and recent CIP history. Our engineer will suggest tests and a corrective plan.